Cloud BMS provides a library of pre-configured FCU (Fan Coil Unit) functional testing workflows. Each workflow commands valves or the fan, reads sensor response, and scores pass or fail against thresholds. Use this page as a parameter and point-requirements lookup. For how FTT decides pass or fail on heating, see What is Functional Testing?. To run one heating test before you schedule a project, see What is Functional Testing?. Select a tab to open the workflow you need.
This workflow will test an FCU for its cooling operation.
  1. First, we display the initial conditions of the equipment.
  2. Then KODE performs precondition checks to ensure the equipment is ready to be tested.
  3. Next we will stop heating by commanding the hot water valve to 0%.
  4. Then we will stop cooling by commanding the chilled water valve to 0%.
  5. Finally we will command the chilled water valve to 100% to start cooling.
Outcome: This test will check a FCU’s ability to deliver cooling when the valve is set to 100%.
Recommended schedule: Run weekly per floor. Run when new FCUs are installed and programmed.
Point requirements:

Required preconditions

  1. FCU Occupancy = Occupied
  2. FCU Fan Cmd% > 5%
  3. Chiller Diff Pressure > 10 PSI
Variations: Heating and cooling workflows with and without fan operation appear later on this page.

Workflow overview

Tuning parameters

If you need assistance with interpreting your results, reach out to the support team at support@kodelabs.com.

Next steps

Run your first test

Run an on-demand FCU heating test and read the score.

VAV workflows

Explore the VAV workflow library for damper, heating, and airflow tracking tests.

AHU workflows

Explore the AHU workflow library for damper, heating, cooling, and VFD tests.

FTT projects

Assign workflows to devices and schedule automated testing.
Last modified on August 18, 2026